System Description
Main Breaker - Located inside the NEMA-4x enclosure the main breaker provides thermal-magnetic overload protection for the system and operator power disconnect.
Secondary Protection - A fast-fuse is provided to protect the PLC and low-voltage operator interface power circuits. Thermal-delay breakers provide secondary protection to the pump motors. The motors are thermally protected to IEC standards.
PLC Functions - The microprocessor based PLC consists of an industrial microcontroller and a 4 line LCD display. The PLC contains a real-time clock with a ten-year rated (field replaceable) battery backup. The controller manages all functions of the fuel purification system.
Low Voltage Operation - Operator interfaces and external circuitry are driven by an isolated NEMA rated 24 volt DC control circuit.
Electrical Enclosure - All electrical switching and control devices are enclosed in weather-tight NEMA rated enclosures.
Wiring - All primary and secondary wiring is 600v rated THHN oil-resistant stranded AWG wire. Liquid-tight conduit is utilized for added safety and reliability. Low voltage wiring is protected to NEMA-4x oil-tight ratings.
Power Switching - IEC rated contactors are provided to handle motor loads and interface to the PLC.
Motors - Motors are TEFC thermally protected, rated for continuous operation to provide years of trouble-free operation.
Circulator Pump - The primary pump is a self-priming positive-displacement type, heavy-duty unit. It is sealed and maintenance free and is a specific-purpose pump designed for operation with diesel and biodiesel fuels.
Waste Pump - The FPS-6 waste pump is a positive-displacement type, heavy-duty unit. It is sealed and maintenance free and is a specific-purpose pump designed for operation with water, diesel, and biodiesel fuels.
Filtration module - the FPS-6 canister is manufactured to ASME standards (non-stamped) and contains three replaceable filter elements. Elements are available from 30 down to 2 microns. Elements are field replaceable, which is easily done by shutting the system down and removing the filter lid. Access is through a hinged top and front cabinet panel. A pressure/vacuum release valve is provided to facilitate vacuum break.
External Operators - A four-line LCD display provides readout of the current time, operating statistics and alarm conditions. Oil-tight selector switches and indicators provide on-off-auto and |
|
indicator functions. Operator lights are LED types with long-life to eliminate frequent bulb changes or missed indications.
Remote Monitoring - Remote contacts are provided for shutdown and alarm operation. Some FPS models include dial-up and network connected remote capabilities.
Indicators and Alarms - An audible alarm is provided to alert personnel to required filter changes or other error conditions. Visible and remote alerts are provided in the event the alarm-silence is activated.
Transducers and Sensors - An electronic transducer is provided to allow the PLC to determine when filter change and other operational errors occur. Flood and waste-overfill sensors provide the PLC with indication of those respective conditions.
Calibration and Startup - The system is self-calibrating based on initial setup parameters. The PLC accepts inputs for tank-size and other configuration data upon installation. When the unit first operates or a filter has been changed the PLC computes ranges that further determine the operating parameters and alarm set points.
Cabinet - The FPS cabinet is a heavy-duty industrial enameled steel cabinet. All components are primed and painted to insure corrosion protection and an attractive finish. The standard colors are White and Green.
Optional Features
Multi-Tank Manifold - A valve manifold and programming option provide capabilities for split and multi-tank applications. The multi-tank option supports from 2 - 5 tanks.
Manual Waste Drain - Deletes the auto-drain feature and holding tank.
Custom Installation - Provides field and engineering support for custom configurations and installations. Contact our engineering staff for special requirements.
Paint Options - OEM and custom paint color schemes for special orders.
Specification : FPS-6-SA-0-0000
[Fuel Purification System : 6 gpm, single manifold, auto-drain, non-custom, standard colors]
Capacity : 6 gallons per minute
Voltage : 10VAC, 60hz, single phase, 20amp circuit
Dimensions : 32" x 24" x 48" (W x D x H)
Weight : Approximately 440lbs.
Shipping Weight : Approximately 440 lbs
|